TRANSFORMER RATING CALCULATION
TRANSFORMER RATING CALCULATION
In this BLOG, we are going t discuss about the Calculation of TRANSFORMER RATING:
For Eg:-
Maximum Load = 400KW.
Diversity Factor = 0.7
Therefore,
Expected Load in KW = 400*0.7 = 280KW
Expected Load in KVA = 280/ 0.9 = 311KVA
(Power Factor Considered as 0.9)
85% Loading Capacity is considered.
Required KVA Rating = 311/ 0.85 = 366KVA
Therefore, 400KVA transformer is used.
(400KVA is the next Available Rating above 366KVA)